Succeful Cases
110V 90A uXcel Ultra Industrial Battery Charger for Substation Upgrade Project in Pakistan
Nov 27, 2026

Project Background

EverExceed supplied a customized uXcel Ultra 110V90A Industrial Battery Charger for a substation upgrade project in Pakistan, replacing the existing DC power equipment.

The DC system supports critical loads such as relay protection, control circuits, circuit breakers and emergency lighting. To address local grid voltage fluctuations and hot, dusty operating conditions, EverExceed adopted a redundant dual-charger configuration, with one charger in operation and the other on standby, ensuring a reliable and continuous DC power supply.

Customized Design Highlights

l Dual-Charger Redundancy

Two chargers share one isolation transformer in a single cabinet, with one operating and the other on standby. The standby unit automatically takes over if the operating charger fails.

l Comprehensive Alarm Indication

Monitors battery overvoltage, undervoltage, AC faults and output breaker trips, with LED indicators for float and equalization charging status.

l Integrated Metering

Equipped with AC voltage, DC voltage, load current and battery current meters for convenient monitoring of operating conditions.

l Low-Ripple DC Output

Output voltage ripple is below 1%, helping minimize interference with sensitive substation equipment and control circuits.

l IP44 Cabinet Design

Features front maintenance access, bottom cable entry with sealed cable glands, and clearly arranged battery and load terminals for easier installation and maintenance.

l Independent Circuit Protection

Battery and load circuits are each equipped with an MCCB-2P 100A circuit breaker, providing independent overcurrent protection.

 

 

Technical Parameters

Topology

6 pulse full bridge thyristor rectifier

Model

uXcel Ultra 110V90A

Input Voltage

400VAC 50Hz

Phase

3 Phase

Rated power

10KW

output voltage

110VDC

Output Current

90A

IP class

IP44

Float Voltage

0V-165V

Boost/Equalize Voltage

0V-165V

Current Limited

100%

Functions and Protection

  • Alarm function: Battery overvoltage, battery undervoltage, AC fault and charger output breaker trip alarms.
  • Protection functions: Over current protection, fuse protection, short-circuit protection and overload protection, etc.
  • Monitoring data: Output DC voltage, output DC current, equalization voltage, float voltage, etc. At the same time, the charger has the function of storing certain data, which can support the customer to check the alarm event and download it at any time.
  • Panel indication: Intelligent touch screen, alarm indicator, operation indication, power indication.
  • Communication: RS485, Modbus RTU.
  • Design service life:The charger can run continuously without trouble for up to 200,000 hours under suitable maintenance conditions.

 

 