Advanced power protection for various applications
EverExceed Corporation establish a long-term partnership with our customers through bring high standard quality control and great customer service for them according
to the demand of international market. We create the valuable new products for our
customers in the long run
PowerLead Series True On-line Double Conversion UPS
Overview EverExceed PowerLead true on-line UPS are designed to protect against a wide variety of potential power problems including spikes, surges, noise, sags, over and under voltage conditions, waveform distortion and extended brownouts, as well as blackouts...even difficult-to-track harmonics and dangerous frequency variations which are common to a tandby generator. It provides superior communication capability via EverExceed hot-swappable SNMP cards. PowerLead allows to be treated as a fully-interactive network node by your network management software.
Feature: ● True on-line double conversion technology with advanced microprocessor control ● Wide input voltage range ● Zero transfer time ● Protection against all types of power problems ● Self test on start of the UPS ● Site wiring fault warning ● On-battery power-on function ● Smart RS232 communication interface or SNMP remote control ● Intelligent slot available ● Maintenance free VRLA battery ● Generator compatible
Ideal Applications: ● Office telecommunications systems ● Voicemail and E-Mail servers ● LAN and WAN servers ● Clustered network equipment: hubs, routers, bridges ● Remote telecommunications units ● Test and diagnostic equipment ● Engineering network servers ● Factory floor protection of microprocessor-controlled equipment
Specifications of PowerLead Series UPS (120VAC)
Model
PL01S
PL01
PL02S
PL02
PL03S
PL03
PL05S
PL05
PL06S
PL06
PL10S
PL10
Power Rating(VA/W)
1000/700
2000/1400
3000/2100
5000/3500
6000/4200
10000/7000
Input
Phase
Single-phase + G
Voltage
120VAC±25%
Frequency
60±5%Hz/40Hz~60Hz(software adjustable)
Power Factor
≥0.95
≥0.98
Output
Voltage
120VAC±1%
Frequency
AC Mode :track utility power Battery Mode: 50Hz/60Hz±0.2Hz
Waveform
Pure Sine wave
Power Factor
0.7
Total Harmonic Distortion
≤3%
(linear load)
≤4%(linear load)
≤2%(linear load)
≤6%
(nonlinear load)
≤7%(nonlinear load)
Battery
Type(Num.)
12V/7.2
Ah(3)
Depend-
ing on
the cappa-
city of external battery
12V/7.2
Ah(3)
Depend-
ing on
the cappa-
city of external battery
12V/7.2
Ah(8)
Depend-
ing on
the cappa-
city of external battery
12V/7.2
Ah
(20)
Depend-
ing on
the cappa-
city of external battery
12V/7.2
Ah
(20)
Depend-
ing on
the cappa-
city of external battery
12V/7.2
Ah
(20)
Depend-
ing on
the cappa-
city of external battery
Recharge Time
5 hours to 90%
5 hours to 90%
5 hours to 90%
5 hours to 90%
5 hours to 90%
5 hours to 90%
Max. Charging Current(A)
1
7
1
8
1
8
4.2
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously Sounding
System instructions
Efficiency
85% (AC Mode)
86% (AC Mode)
90% (AC Mode)
83% (Battery Mode)
Transfer Time
AC to DC:0ms Inverter to Bypass:2.5ms (Typical)
Communication Interface
Smart RS232: Software support Windows95/98/2000/NT/XP/Novell/Linux; SNMP(Option):Power management from SNMP management and web broser
Temperature
(Operating): 0~40℃
Relative Humidity
20%~90% noncondensing
Audible Noise
≤45dB at 1meter
≤50dB at 1meter
≤55dB at 1meter
Physical
Dimension (W×D×H) mm
145×400×220
192×460×340
240×545×445
Net Weight(kgs)
13
7
32
15
33
16
95
60
95
60
101
66
Remark
PL-xK Series represent extended backup models
Specifications of PowerLead Series UPS (220VAC)
Model
PL01S
PL01
PL02S
PL02
PL03S
PL03
Power Rating(VA/W)
1000/700
2000/1400
3000/2100
Input
Phase
Single-phase + G
Voltage
160VAC~300VAC
Frequency
40Hz~60Hz(software adjustable)
Power Factor
≥0.95
Output
Voltage
220VAC/230VAC±2%
Frequency
AC Mode :40Hz~60Hz Battery Mode: 50Hz±0.2Hz
Waveform
Pure Sine wave
Power Factor
0.7
Total Harmonic Distortion
≤3%(linear load)
≤4%(linear load)
≤6%(nonlinear load)
≤7%(nonlinear load)
Battery
Type(Num.)
12V/7.2Ah
(3)
Depending on the cappacity of external battery
12V/7.2Ah
(3)
Depending on the cappacity of external battery
12V/7.2Ah
(8)
Depending on the cappacity of external battery
Recharge Time
5 hours to 90%
5 hours to 90%
5 hours to 90%
Max. Charging Current(A)
1
7
1
8
1
8
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously Sounding
System instructions
Efficiency
85% (AC Mode)
86% (AC Mode)
83% (Battery Mode)
Transfer Time
AC to DC:0ms Inverter to Bypass:2.5ms (Typical)
Communication Interface
Smart RS232: Software support Windows95/98/2000/NT/XP/Novell/Linux; SNMP(Option):Power management from SNMP management and web broser
Temperature
(Operating): 0~40℃
Relative Humidity
20%~90% noncondensing
Audible Noise
≤45dB at 1meter
≤50dB at 1meter
Physical
Dimension (W×D×H) mm
145×400×220
192×460×340
Net Weight(kgs)
13
7
32
15
33
16
Remark
PLX Series represent extended backup models
Specifications of PowerLead Series UPS (220VAC)
Model
PL05S
PL05
PL06S
PL06
PL10S
PL10
3PL10
3PL15
3PL20
Power Rating(VA/W)
5000/3500
6000/4200
10000/7000
10000/7000
15000/10500
20000/14000
Input
Phase
Single-phase + G
Three phase+G
Voltage
176VAC~276VAC
380VAC±15%
Frequency
40Hz~60Hz(software adjustable)
Power Factor
≥0.98
Output
Voltage
220VAC/230VAC±2%
Frequency
AC Mode :40Hz~60Hz Battery Mode: 50Hz±0.2Hz
Waveform
Pure Sine wave
Power Factor
0.7
Total Harmonic Distortion
≤2%(linear load)
Battery
Type(Num.)
12V/7.2
Ah
(20)
Depend-
ing on
the cappa-
city of external battery
12V/7.2
Ah
(20)
Depend-
ing on
the cappa-
city of external battery
12V/7.2
Ah
(20)
Depend-
ing on
the cappa-
city of external battery
Depending on the cappacity of external battery
Recharge Time
5 hours to 90%
5 hours to 90%
5 hours to 90%
Max. Charging Current(A)
4.2
Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously Sounding
System instructions
Efficiency
90% (AC Mode)
83% (Battery Mode)
Transfer Time
AC to DC:0ms Inverter to Bypass:2.5ms (Typical)
Communication Interface
Smart RS232: Software support Windows95/98/2000/NT/XP/Novell/Linux; SNMP(Option):Power management from SNMP management and web broser