General Specification of UPS Applied to Electric Power Systems
|
| Modle |
PC10S |
PC15S |
PC20S |
PC30S |
PC40S |
PC50S |
PC60S |
PC80S |
Rated Power |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
80KVA |
Working |
Online, static bypass switch(seamless transfer), double conversion technology, output isolated from input |
AC Input |
Voltage |
380V±20% 3 wires+N+G |
Frequency |
50Hz±10% |
Maximum Input Current |
19A |
29A |
38A |
57A |
76A |
95A |
114A |
152A |
Power Factor |
0.95(with input filter) |
Soft Start |
0-100% ¡¡1sec |
Bypass Input |
Voltage |
220V±15% L+N+G
|
Frequency |
50Hz±5%
|
Transfer Time |
Inverter / bypass(overload)0ms |
DC
System |
DC Voltage |
220V or 384V |
384V |
Floating Charge Voltage |
DC220V: 250V; DC384V: 432V
If it needn't charge, there should be a reversed diode |
432V |
Cutoff Voltage |
DC220V: 190V; DC384V: 336V |
336V |
AC Output |
Voltage |
220V±1%(steady load) L+N+G |
Frequency |
50Hz±5%(utility power) 50Hz±0.05%(battery backup) |
Power Factor |
0.8lagging |
Output Waveform |
Sine wave |
Total Harmonic Distortion |
Linear load<3% non-linear load <5% |
Voltage Transient (Step Load) Response |
±5% for 100% step load change |
Voltage Recovering Time |
<10ms(±5%) |
| Overload Capability |
125% 10min 15% 1min >150% 200ms |
| System |
Efficiency |
>91%(10-20K) |
>95%(30-80KVA) |
Communication Interface |
RS 232/RS 422 |
Operating Temperature |
0℃ to 40℃(32℉ to 104℉) |
Relative Humidity |
0~90% non-condensing |
Audible Noise |
50dB |
63dB |
65dB |
Dimensions D×W×H(mm) |
600X800X1400 |
850X950X1800 |
900X1200X1800 |
Weight(KG) |
198 |
253 |
311 |
380 |
470 |
530 |
620 |
860 |
Product specifications are subject to change without further notice. |