General Specifications Of PowerGuiding |
Model |
PG10 |
PG15 |
PG20 |
PG30 |
PG40 |
PG60 |
Power |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
60KVA |
Input |
Voltage |
380V±20% |
Frequency |
50Hz±5% |
Phase |
3 Phase+N+G |
Control |
IGBT SPWM |
Output |
Voltage |
220V±2% |
Frequency |
50Hz±0.5% (Main Power 50Hz±1Hz) |
Waveform |
Sine wave, THD<3% (0-100% linear load) |
Overload
Capability |
120% rated current: switch to bypass after 60 seconds;
150% rated current: switch to bypass after 10 seconds |
Power Factor |
0.8 lagging |
Crest Ratio
|
3:1 for rectifiable load |
Response Time |
±2% (100% load change) |
Transfer Time |
0ms |
Battery |
Type |
Sealed lead acid maintenance free battery |
Backup Time |
Standard backup time 5-10 minutes, can be extended to 8 hours |
Charge Time |
90% capacity in 7-10 hours |
| DC Voltage |
192VDC |
360VDC |
System Efficiency |
>87% |
Inverter Efficiency |
>93% |
Protection |
Limit current output on overload, Short circuit protection, Spike protection, Safety complies with CCEE EN60950 |
EMC Requirement |
Complies with EN59001 |
Display |
LED |
Input / bypass / inverter / battery / overload |
Alarm |
Main Power Fault |
Alarm beeps every 4 seconds |
Low Voltage |
Alarm beeps every second (battery exhaust) |
Overload |
Alarm beeps two for every second
|
UPS Fault |
Continuous beeping sound |
Interface |
RS232 |
Supports WINDOWS95/98/2000/NT/XP, NOVELL NETWARE, UNIX, SNMP optional |
|
0℃ to 40℃ (32ºF to 104ºF)
|
Humidity |
0-90% non-condensing |
Acoustic Noise |
<60dB |
|
Weight (W/O Battery) |
181kgs |
235kgs |
285kgs |
325kgs |
365kgs |
480kgs |
Dimensions (WxHxD)(mm) |
550x980x440 |
560x1220x720 |