EverExceed Corporation establish a long-term partnership with our customers through bring high standard quality control and great customer service for them according
to the demand of international market. We create the valuable new products for our
customers in the long run
EverExceed Tubular OPzV Range Gel
EverExceed tubular plate OPzV Range gelled, maintenance free sealed valve regulated lead acid rechargeable batteries offer their superior performance and reliability in both controlled and harsh uncontrolled environments. EverExceed state-of-the-art manufacturing facilities with wealthy experience ensure it's tubular OPzV gelled batteries reliable performance, safety, outstanding battery life and value. Each cell is 100% factory tested. EverExceed tubular OPzV batteries can be used in float or deep cycle (1500 x 80%)service and have a design life of 20 years at 20°C. EverExceed tubular OPzV batteries can be stored up to 2 years at 20°C without fresh charging.
Specification
● Positive electrode: Tubular Plate with antiminy-free special alloy
● Negative electrode: Flat Grid plate
● Electrolyte: Suspended Thixotropic Gel
● Container & Cover SAN Optional V-0
● Separator: Microporous plastic
● Float Voltage: 2.23 VPC +/- 1% at 20 C
Max. Charge Voltage: 2.40 VPC at 20 C
● Safety Valve: 1-3 PSI Self-Resealing
● Terminals: Integral Copper Insert
● Interconnects: Insulated cables
20 years design life
Tubular plate
Single cell
Nominal capacity:
200 - 3000Ah
deep discharge recovery
Maintenance free
Recycleable
Valve regulated lead-acid
General Specifications
Model No.
C10 Ah 1.80
C5 Ah 1.75
C3 Ah 1.75
C1 Ah 1.70
Ri (1) m W
lk (2) A
Outline Dimensions (mm/inch)
Lenght
Width
Height(h2)
Height(h1)
2V 4 OPzV 200
210
179
158
117
0.94
2235
103
206
380
354
20
2V 5 OPzV 250
260
223
197
145
0.78
2710
124
206
380
354
24
2V 6 OPzV 300
310
268
236
174
0.60
3420
145
206
380
354
29
2V 5 OPzV 350
370
331
285
212
0.61
3450
124
206
496
470
31
2V 6 OPzV 420
450
397
342
255
0.49
4220
145
206
496
470
36
2V 7 OPzV 490
520
463
399
297
0.51
4100
166
206
496
470
42
2V 6 OPzV 600
630
555
492
369
0.44
4750
145
206
671
645
50
2V 9 OPzV 630
660
585
516
387
0.42
4850
254
210
496
470
54
2V 7 OPzV 700
730
645
573
431
0.38
5500
254
210
496
470
60
2V 11 OPzV 770
810
705
630
473
0.35
6300
254
210
496
470
66
2V 8 OPzV 800
820
740
654
491
0.30
6820
191
210
671
645
68
2V 10 OPzV 1000
1030
925
819
614
0.25
8200
233
210
671
645
82
2V 12 OPzV 1200
1230
1110
984
738
0.21
9850
275
210
671
645
97
2V 12 OPzV 1500
1550
1430
1269
920
0.19
10500
275
210
795
821
120
2V 16 OPzV 2000
2070
1905
1713
1226
0.15
14000
399
212
797
772
160
2V 20 OPzV 2500
2580
2385
1986
1533
0.12
17500
478
212
797
772
200
2V 24 OPzV 3000
3090
2855
2571
1840
0.10
21000
576
212
797
772
240
(1),(2)internal resistance and short - circuit - current from IEC 896-1
4 OPzV 100 up to 6 OPzV 600
6 OPzV 2000
20 OPzV 2500 up to 24 OPzV 3000
Design
positive electrode
tubular - plate with a woven polyester gauntlet and solid grids in a corrosion- resistant PbCaSn - alloy
negative electrode
grid - plate in a PbCaSn alloy with long - life expander material
separation
microporous separator
elektrolyte
s ulphuric acid with a density of 1,24 kg/l, fixed as GEL by fumed silica
container
high impact, halogen-free SAN (Styrol-Acryl-Nitril), grey coloured, UL rating 94HB
lid
high impact, halogen-free SAN (Styrol-Acryl-Nitril), grey coloured, UL rating 94HB
valve
valve with flame arrestor
opening pressure approx. 100 mbar,
closing pressure approx. 50 mbar
pole - bushing
100% gas- and electrolyte-tight, sliding-pole
kind of pole
M10 brass insertion
connectors
flexible insulated copper cables, with cross-section of
35, 50, 70 or 95 mm²
kind of protection
IP 25 regarding DIN 40050, touch protected according VBG 4
Charging
IU - characteristic
Imax without limitation
U = 2,23 to 2,25V/cell +- 1%, between 10°C and 45°C
D U/D T = -0,004 V/K below 10°C in the monthly average
boost charge
U = 2,35 to 2,40V/cell, time limited
charging time
up to 90% 6h with 1,5*I10 initial current, 2.23 V/cell, 50% C10 discharged
Discharge characteristics
reference temperature
20°C
initial capacity
100%
depth of discharge (DOD)
normally up to 80%
deep discharges
more than 80% DOD or discharges beyond final discharge
voltages (dependent on discharge current) have to be avoided
Maintenance
every 6 months
check battery voltage, pilot cell voltage, temperature
every 12 months
record battery and cell voltages and temperatures
Operational data
operational life
> 15 years at 20°C
>7,5 years at 30°C
>4 years at 40°C
maintenance-free
no topping-up water during operational life
IEC 896-2 cykles
1200
self-discharge
app. 2% per month at 20°C
recovery after deep discharge
very good
operational temperature
-20°C to 45°C
recommended 10°C to 30°C
short-time 45°C to55°C
ventilation requirement
25% (f1=0,5 x f2=0,5)due to VDE 0510 part 2
standard
DIN 40 742 part 1
tests according
IEC 896-2,
safety standard
VDE 0510, part 2
transport
no dangerous goods during air-, sea- and land transport