| General Specifications of MPPT PV Range Grid-on Inverter |
| Model |
MPV 2010 |
MPV 2025 |
MPV 2030 |
MPV 2040 |
MPV 2050 |
MPV 2075 |
MPV 2100 |
MPV 2200 |
MPV 2400 |
MPV 2600 |
MPV 2800 |
| Input |
Max.photovoltaic array power (Wp) |
1.2kw |
3kw |
3.6kw |
4.8kw |
6kw |
9kw |
12kw |
24kw |
48kw |
72kw |
96kw |
| Max.photovoltaic array open-circuit voltage |
500V |
| MPPT voltage range (V) |
150 to 480V |
| Max.array input current (A) |
7.4 |
17.7 |
22.1 |
29.5 |
35.4 |
53 |
71 |
141.6 |
283 |
424.8 |
566.4 |
| Output |
Phase |
Single-phase three-wire |
Three-phase Five-wire |
| Rated output power |
1kw |
2.5kw |
3kw |
4kw |
5kw |
7.5kw |
10kw |
20kw |
40kw |
60kw |
80kw |
| Maximum output power |
110%×Rated Power |
| Allow grid voltage range (V) |
198 to 242V (Can be set) |
| Allow grid frequency range (Hz) |
49.5 to 50.5Hz (Can be set) |
| Rated output Current (A) |
4.5 |
11A |
15A |
20A |
22A |
34A |
45.4A |
30.3 |
60.6 |
90.9 |
121.2 |
| Total current distortion rate (THD) |
≤4% |
| Output power factor |
0.99 |
| Max. effciency |
>92% |
>94% |
| Europe efficiency |
>90% |
>92% |
| MPPT tracking efficiency |
>98% |
| Electromagnetic compatibility |
IEEE929/EN61000 |
| Function parameters |
Detection of Anti-island effect |
Have active and passive detection of island |
| Power Grid short-circuit protection |
Protection restart automatically when the incorporation grid electric current is bigger than 150% nominal current |
| LCD display |
Real-time parameters, such as input and output voltage, frequency, output power, output current, working status and so on |
| Communications and centralized monitoring |
RS232/RS485/SNMP(Optional) |
Electrical energy measurement and
electricity price calculation |
Have the electrical energy measurement and the electricity price calculation function, can be designed the unit price and the currency |
| General Parameters |
Standby power loss (W) |
<10W |
| Cooling Mode |
Air-cooled(indoor),the natural cooled (outdoor) |
Air-cooled (indoor) |
| Protection Level |
IP21 (Indoor), IP55(Outdoor) |
IP21 (Indoor) |
| Ambient temperature (℃) |
-20 to 50℃ |
| Noise |
<40dB |
<50dB |
<60dB |
| Insulation resistance (input and output to ground) |
>50MΩ |
| Insulation pressure resistance (input and output to ground) |
2000VAC/10mA |
| Insulation pressure resistance (input vs output) |
1500VAC/10mA |
| Dimension (D×W×H)mm |
653× 327× 130 |
653× 327× 151 |
653× 327× 151 |
653× 327× 221 |
653× 327× 221 |
800×600×2600 |
800×600×2600×2pc. |
| Weight (kg) |
12.5 |
15.2 |
15.2 |
30.4 |
30.4 |
113 |
129 |
193 |
321 |
449 |
577 |