General Specifications of DigitalActive |
Model |
DA750 |
DA1000 |
DA1500 |
DA2500 |
DA3500 |
DA5000 |
DA750RM |
DA1000RM |
DA1500RM |
DA2500RM |
DA3500RM |
DA5000RM |
Rated Power(VA / W) |
750VA(525W) |
1000VA(700W) |
1500VA(1050W) |
2500VA(1750W) |
3500VA(2450W) |
5000VA(3500W) |
Input |
Input Voltage Range |
164V~271V divided to 3 online configurable levels(user congfigurable 110V input) |
Input Frequence |
43Hz~58Hz |
Maximum Input Current |
3.2A |
4.2A |
6.4A |
12.7A |
17.8A |
25.6A |
Input Type |
L+N+G(single phase 3 wires) |
Output |
Output Voltage Range |
Utility Power |
220V(+10%~-10%) |
Battery Backup |
220V±2%(configurable 110V ) |
Output Frequence |
Utility Power |
The same as utility power |
Battery Backup |
50Hz(or 60Hz)±0.1Hz |
Total Harmonic Distortion(Battery) |
<2%(linear) <5%(no-linear) |
Output Current Peak Factor |
3:1 |
Transfer Time Upon Outage |
<4ms |
Battery |
Maximum Discharge Current |
30A |
40A |
60A |
58A |
81A |
110A |
Typical Backup Time |
5-10minutes(user configurable, optional additional external batteries for up to 1-8 hours backup time |
Nominal Bat. Voltage |
Standard |
24Vdc |
24Vdc |
24Vdc |
48Vdc |
48Vdc |
48Vdc |
Rack Mount |
48Vdc |
24Vdc |
24Vdc |
48Vdc |
96Vdc |
48Vdc |
Typical Recharge Time |
10hours over 90%(standard configuration) |
Protection Functions |
Low Battery Protection |
Self-regulation the value of low battery according to the discharging rate. |
Overload Protection |
Battery Backup |
>105%,protect after 10s; >120%, protect after 3s; >150%,protect after 200ms |
Utility Power |
If >105% alert, if>120% switch to bypass power after 1min |
Output Under/Over Voltage Protection |
Shut the output if <160V or >260V |
Short Circuit Protection |
Shut the output and alert |
EMC Requirement |
Meets GB 7260.2 |
Operating Enviroment |
Temperature:-20℃~ 40℃ (-4℉ to 104℉) |
Elevation:0~+3000(0~1000feet) |
Relative Humidity:0%~95%, non-condensing |
Other Functions |
Open-circuit battery test; periodic automatic battery test |
Low battery protection throat; automatic startup on condition that utility power resume |
Cold start on battery |
Stand-alone communication, optional network management |
Software-based functions: periodic selftest, scheduled startup and shutdown, autosavement of the document, realtime parameter display, alert via telephone or mobilephone note to view the running status of UPS |
Display the running status of UPS on LCD; realtime modify system parameters |
Automatic transfer to floating charge mode from const-current charge mode |
On-line configurable charge mode for different configuration of batteries |
Intelligent fan cooling |
Provides three choice of charge mode |
Provides audible and visual alarm on low battery, battery backup overload, fault conditions |
Parameter modified online can be permanently kept |
System Performance |
Power Factor |
0.7 |
Operating Efficiency |
>98% |
Dimensions (H×W×L) mm |
Standard |
327×162×500 |
402×205×578 |
470×248×668 |
Rack Mount |
88x482.6x460 |
132.5x482.6x660 |
266x482.6x650 |
Weight(KG) |
Standard |
16/25(Including batteries) |
18/28(Including batteries) |
18/28(Including batteries) |
27.5/52(Including batteries) |
31/55.5(Including batteries) |
49/79(Including batteries) |
Rack Mount |
26 |
30 |
30 |
46 |
50 |
80 |
| The standard model including: with batteries inside, with external batteries. RM means the dimension is Rack Mount. |
| Product specifications are subject to change without further notice. |