Advanced power protection for various applications
EverExceed Corporation establish a long-term partnership with our customers through bring high standard quality control and great customer service for them according
to the demand of international market. We create the valuable new products for our
customers in the long run
Overview: The PowerChampion serial three phase UPS offers advanced technology that increase performance and reliability; three high speed DSP with completed digital control fully ensure high quality of power supply, high input power factor makes UPS greed energy saving power. It also offers humanization design; full front access of serviceability, user-friendly interface.
Applications: ● ISP (Internet Service Provider) ● IDC (Internet Data Center) ● Computing center ● Bank ● Server center ● Precise equipment and etc
Features: ● 12 pulse rectifier ● Compatible with utility of 200/208/380/400/415VAC, 50/60Hz ● Green power technology, high input power factor, low current THD, high efficiency ● Online double conversion, offering load with best power quality ● intelligent battery management, extending battery lifetime ● Large LCD display, friendly human machine interface ● All kinds of option include main back feed protection, bypass back feed protection, battery leakage protection, battery start kit and output isolation transformer lighting protection kit ● Intelligent self-diagnose function, all kinds of fault protection , large capability of history record storage ● configured with top and bottom cable connection ● Full front maintenance, saving space ● Redundant design of power model fans, increasing the system reliability ● Modularized design of subsystem, convenient field maintenance ● Fully digital control with three DSP including IGBT rectifier, inverter, charger ● Wide input voltage window, compatible with different utilities ● Support all kinds of load, high overload capability
Technical Parameter:
Model
PW10L
PW15L
PW20L
PW30L
PW40L
PW60L
PW80L
PW100L
PW120L
PW160L
PW200L
Capacity
10KVA
15KVA
20KVA
30KVA
40KVA
60KVA
80KVA
100KVA
120KVA
160KVA
200KVA
Main Input
Input voltage
200/208/380V/400V/415V(line to line), 50/60Hz
Input connection
3Ph+N+PE
Power factor
>0.99
Input cuurent THD(Total Harmonic Distortion)
<3%
Input voltage window
+20%~-20%, full load
-20%~-40%, power derating between 100% to 70%
Frequency window
40-70HZ
Bypass input
Input voltage
200/208/380V/400V/415V
Input voltage window
+20%--20%, full load
-20%--40%, power derating between 100% to 70%
Frequency window
±3Hz (adjustable)
Output
Voltage precision
±0.5% (balance load),2% (unbalance load)
Output voltage transient
2%(0~100% load step)
Voltage THD(Total Harmonic Distortion)
THD<0.5%(linear load),THD<4%(nonlinear load)
Power factor
0.8
Frequency tracking range
50/60Hz±3Hz, adjustable
Frequency precision (free running)
±0.01%
Phase tolerance
120°±0.5° (balance and unalance load)
Voltage unbalance degree (100% unbalance load)
±3%
Frequency tracking speed
0.5Hz/s to 5Hz/s, adjustable
Crest factor
3:1
Overload capabiltiy
105% long time operation
110%, transfer to bypass after 1hour
125%, transfer to bypass after 10 minutes
150%, transfer to bypass after 1 minute
>150%, transfer to bypass after 200ms
Bypass overload capability
150%, long time operation
150%< load <180%, last for more than 1 minute
>1000%, last for more than 100ms
System
System efficiency
Normal mode: 95%
ECO mode: 99%
Battery mode efficiency
95%
Battery configuration
12V, 40PCS (38~42pcs acceptable)
Display
LCD+LED, Touch screen and keyboard
EMI
IEC62040-2
EMS
IEC61000-4-2(ESD)
IEC61000-4-3(RS)
IEC6100-4-4 (EFT)
IEC6100-4-5 (Surge)
Insulation resistance
>2M (500VDC)
Dielectric strengh
(input,output to PE)2820Vdc, leakage current lower than 3.5mA, no flashover in 1 minute
Surge protection
Comply with IEC60664-1 class IV, endure surge of 1.2/50us + 8/20us higher than 6KV/3KA