Power Your Applications
 
       
 

EverExceed Corporation establish a long-term partnership with our customers through bring high standard quality control and great customer service for them according to the demand of international market. We create the valuable new products for our customers in the long run





 
 
Emergency Power Supply
 
Three Phase EPS Single Phase EPS
Overview
Emergency Power Supply(EPS) is designed for a load to provide backup power solution, it applies to fire, electricity, metallurgy, petroleum, chemical industry, schools, hospitals, mines, and all use of automatic control of the premises, providing them with safe and reliable power to protect. When the mains is normal, after each vote in the municipal electric power to the load switching device, while an intelligent back-up battery charger for charging, when the city electricity interruption or exceeds the normal voltage range, by the inverter controller provides the signal to start reverse variable power supply, while inter-switch device to switch to the inverter output, continue to provide sinusoidal alternating current to the load, when the city returned to normal when the power, EPS automatically restore electricity supply.
Catalogue Download
 
Feature:
Advanced DSP digital control enhances reliability, stability;
Higher than 99% efficiency at main mode save energy.
Intelligent battery management functions, fully automatic switch between constant charge and float charge, regular battery detection, single battery voltage display, and battery fault alarm functions prolong battery life;
Transformer isolated output provides adaptability, impact good, high reliability, and the arbitrary load;
RS232, SNMP (option) provides network management and communications, dry contact remote monitoring, control, interactive control with other equipment (option);
Intelligent fan control, low noise and long life;
Humanized big touch screen LCD provides intuitive view of intelligent icon status of the flow chat, events records and menu operation.
Two utility power switch function enables automatic or manual switching between main power and secondary power.
Automatic switching, unattended and less than 0.1 seconds transfer time meet all need of emergency supply power.
Perfect protection has output over/low load protection, battery over charge/discharge protection; short circuit protection; over-temperature protection and so on, as well as alarming function.

 
Specifications of Emergency Power Supply 
Rating PE-T 2.2K PE-T 3.7K PE-T 5.5K PE-T 7.5K PE-T 11K PE-T 15K PE-T 18.5K PE-T 22K PE-T 30K PE-T 37K PE-T 45K PE-T 55K
input voltage 380Vac±25﹪(customizable)
input frequency 50hz
output wave(emergency mode) sine wave
output voltage Synchronized with the main power;380V±2%(emergency mode)( customizable)
output frequency Synchronized with the main power, emergency mode 50Hz±1%
output frequency precision ±5%(load from 0~100% or 100~0%)
instantaneous Recover time 20ms(load from 0~100% or 100~0%)
voltage distortion linear:≤2% non-linear:≤5%
transform time ≤0.1s
DC input voltage 96VDC 288/384 VDC 384/768 VDC
efficiency(float charge) ≥99%
efficiency(emergency mode) ≥85﹪
runtime >90minutes(customizable)
cell testing  auto testing single cell voltage when LCD display single cell voltage
display LCD+LED
display precision ±2%
protection Short circuit\overload\low voltage\over temp, 
overload capability <120%:continues work; >125%:delay 10s
communication dry contact(options);RS232;SNMP(options)
auto restart After turning off because battery is low voltage, switching main mode if utility power recovers
environment temp:0℃~40℃  humidity
:0%~95% non-condensing altitude:0~3000m
Dimension(W×D×H) mm 650×470×1500 800×470×1950 800×620×2200 800×620×2200
Weight(kg) 39.8 53 67.2 69 86 104 158 162 171 179 180 182